Start networking and exchanging professional insights

Register now or log in to join your professional community.

Follow

Is the Differential Protection on transformer provides protection outside the protection zone ?

user-image
Question added by Adnan Ahmad , Senior Electrical Engineer , Engro Polymer and Chemicals ( Petrochemical Plant)
Date Posted: 2016/05/21
Himadri Roy
by Himadri Roy , MANAGER ELECTRICAL , STEAG ENERGY SERVICES

Generally Differential protection of a transformer is designed to operate fault within the protected zone. It will not operate out side Zone fault, but if outside zone fault is to huge & to avoide Saturation of CT's may mal operation the Relays, to prevent that we tend to use slope/bias characteristics or stabilizing resistor or metrosil etc according to nature of protection

Jerry Victor
by Jerry Victor , Technical Pre-Sales Engineer , Al Mazroui ICAS LLC

No, Differential Protection does not provide protection otuside the zone. It compares the phase difference and magnitude entering and leaving the protected zone. Differential relay works on the principle of Kirchoff's current law, the differential current measured between incoming and outgoing current must be negligible during stable condition, in case of fault the relay will sense the differential current and initiate breaker trip.

The Differential Protection does not Provide protection outside the differential zone.

No the Differential Protection provides protection to Inside the differential Zone Only. any fault outside the zone will not be protected.

More Questions Like This

Do you need help in adding the right keywords to your CV? Let our CV writing experts help you.