Which communication protocol do you use in your company OPC or Modbus? Which one do you prefer and why?

Communication protocol survey

what other to prefer to use and why the prefer certain one.

for me i prefer OPC because it take less time to commissioning the system 

user-image
تم إضافة السؤال من قبل Hasan Zainy , Control / Instrumentation Filed Service Engineer , GE
تاريخ النشر: 2016/02/19
Hassan Idami
من قبل Hassan Idami

I agree with Yazan Al-Najjar. It depends on your application, not on what other people use in their companies.

Actually, we use both of them in our company, but the choice of the protocol in each case has been made according to its requirements

Yazan Al-Najjar
من قبل Yazan Al-Najjar , Sr.Control System Engineer (Siemens Automation Specialist), FS Eng (TÜV Rheinland, # 13264/ 16, SIS) , Silvertech Middle East

It depends on the application requirement,

1- OPC support time while modbus is not logging time for each signal.

2- OPC provides information about signal quality while modbus is providing the values only.

3- Modbus communication can operate 127 register for each R/W operation while OPC R/W each tag separately.

4- Redundant Modbus communication can be configured without using third party software while OPC usually need third party software to achieve redundancy.

5- Both of them are easy to configure but Modbus communication requires knowledge of modbus Function Codes (1, 2, 3, 4, 5, 15,  6,16 ...) to establish the communication.

Khalid  Imtiaz
من قبل Khalid Imtiaz , Design & Application Engineer , Intech Automation & Intelligence

We mostly ued Kepwaer OPC Server for Modbus and all other 3rd PARTY PLC communication.Irecomend you this is best well servies and large range of Communication Drivers Available.

Sachin Bhadesia
من قبل Sachin Bhadesia , Sr. Control Systems Engineer , Fluor Corporation

Well it purely depends on client's requirements.

However, it would be good to have Modbus protocol when the data to be transferred is limited. Sometimes using different protocols may lead to have specialized competencies during commissioning as well as during maintenance.

SUNIL KUMAR JAIN SUNIL
من قبل SUNIL KUMAR JAIN SUNIL , E & I Engineer , TECHNOCRAFT General Trading & Contracting Company Kuwait

MODBUS COMMUNICATION USING MEDIA CONVERTOR LIKE PHOENIX CONTACTS